Detailing calculators
4 detailing calculators: roof drainage downpipes, roof screed falls, insulation thickness from a target U-value, and movement joint width. With code sources and jurisdiction notes.
What this group solves
This group sizes the building fabric: how a roof drains, how thick the fall screed and insulation go, how wide a movement joint needs to be. The formulas are ordinary physics; the inputs are jurisdiction-specific. Storm intensity comes from a local formula, U-value limits from a climate zone, joint spacing from the structural type and joint width from a standard detail. Move country and the formula holds while every number changes.
All four tools name their source. Downpipe capacity comes from GB 50015 Table 4.9.22, where plastic and cast iron are two separate tables and a nominal DN100 differs by 36% between them. Insulation is back-calculated with GB 50176 surface resistances, so Ri is 0.11 where EN ISO 6946 would use 0.13. Movement joints are controlled by the spacing limits in GB/T 50010 Table 8.1.1, with the width detailed at 20-30 mm rather than computed straight from thermal movement.
The way to use this group is to fix the jurisdiction-specific inputs first and apply the formula second. For the same 1000 m² roof at 300 L/(s·ha), plastic De110 downpipes need two and cast iron DN100 needs three — the formula is untouched, only the material changed. Confirm the pipe material, the surface resistances, the masonry type and the climate zone before reading the answer, or the result will look precise while being based on the wrong table.
Which one for your case
| I know the roof area and local storm intensity, and need the downpipe count | Roof Drainage Calculator |
| I know the roof area and fall, and need the screed volume | Roof Slope Layer Calculator |
| I have a target U-value and need the insulation thickness | Insulation Thickness Calculator |
| The structure is too long and I need joint width and spacing | Movement Joint Width Calculator |
Where this group goes wrong
- Sizing downpipes from a blanket "DN100 carries about 15 L/s" without checking the material — plastic De110×3.2 carries 15.98 L/s but cast iron DN100 only 11.77, a 36% gap. Sizing to the larger figure leaves the roof a third short of downpipes and it ponds in a storm.
- Mixing surface resistances between codes — GB 50176 uses Ri 0.11 while EN ISO 6946 uses Rsi 0.13, which shifts the thickness by about 1 mm and leaves the energy report disagreeing with the detail.
- Doubling thermal movement and calling it the joint width — a 60 m structure over 30°C works out at 56 mm where a standard expansion joint is detailed at 20-30 mm. An oversized joint forces a different waterstop and cover plate, and still leaks air and water.