Flow Rate Converter

m³/h, L/s, L/min and GPM — every unit at once.

Inputs

Result

Formula

Base1 m³/h = 1000 L/h = 0.2778 L/s
Per second1 L/s = 60 L/min = 3.6 m³/h
US units1 GPM = 3.785 L/min = 0.2271 m³/h
Air1 CFM = 1.699 m³/h
Pipe sizingQ = A × v with A = πd²/4
10 m³/h is 2.778 L/s, 166.67 L/min, 44.03 GPM or 5.886 CFM. A DN50 pipe at 1.5 m/s carries about 10.6 m³/h — the same order.

Flow rate unit reference

UnitSymbolIn m³/hIn L/sTypical use
Cubic metre per hourm³/h10.2778Pumps, cooling towers
Cubic metre per secondm³/s36001000Rivers, large flows
Litre per secondL/s3.61Supply design
Litre per minuteL/min0.060.01667Terminal use
US gallon per minuteGPM0.22710.0631Imported equipment
Cubic foot per minuteCFM1.6990.4719Ventilation, fans

FAQ

Why do pumps come in m³/h when pipes are sized in L/s?
Different habits: pump makers rate hourly output while hydraulic tables are per second, a factor of 3.6. Convert everything to L/s before reading tables, or 10 m³/h gets mistaken for 10 L/s and the pipe comes out 2.7 times too big.
What is an economic water velocity?
Usually 1.0-1.5 m/s, 0.6-1.0 below DN50 and 1.2-2.0 above DN100. Too slow and sediment settles with long stagnation; too fast and head loss grows with the square of velocity, bringing noise and erosion. Fire mains may run to 2.5 m/s.
How do I convert GPM to m³/h quickly?
Multiply by 0.227, or roughly 0.23; the other way, 1 m³/h ≈ 4.4 GPM. Imported pumps and cooling towers rate flow in GPM while domestic fittings are chosen in m³/h, and a conversion slip shows up as insufficient cooling water and high-temperature alarms.