Column Confinement Zone Calculator

Confinement length, hoop spacing and bar size for each detailing class.

Quick answer

With the default inputs: Column long side 500 · Clear height between beams 3600 · Detailing class Class 2 etc.Column end confinement length 600 mm

Edit the inputs below to recalculate.
Hoop zoneHoop zoneColumn long side mmClear height betwe mm
The hoop zone is the greater of clear height/6, the longer section side and 500 mm; at the lowest storey base it is at least clear height/3. Both ends shown are densified.

Inputs

Result

Column end confinement length
600mm
Section long side hc500mm
Clear height Hn3600mm
Hn / 6600mm
Minimum500mm
Largest of three600mm
Governed byGoverned by Hn/6
Max hoop spacing100mm
Min hoop diameter8mm
Ground storey base1200mm
Each side of rigid floor500mm
Both ends, excl. joints1200mm
Unconfined length2400mm

Based on GB 50011-2010 (2016 edition) clause 6.3.9 and Table 6.3.7-1. Full-height confinement is required for columns with shear span ratio ≤ 2, clear height to section depth ≤ 4, transfer columns and corner columns of class 1 and 2 frames. The base of the ground storey needs ≥ Hn/3. Hoop leg spacing limits are 200 mm for class 1, 250 mm (or 20 db, whichever is larger) for classes 2-3 and 300 mm for class 4. Where longitudinal reinforcement exceeds 3%, hoops shall be at least 8 mm, spaced within the lesser of 6d and 100 mm, and closed by welding.

Formula

End zone lengthl = max(long side hc, Hn/6, 500 mm)
Ground storey basenot less than Hn/3
Rigid floor500 mm above and below
Max spacingC1 min(6d,100); C2 min(8d,100); C3-4 min(8d,150)
Min diameterC1 10 mm; C2-3 8 mm; C4 6 mm
Full heightcorner, transfer, low shear span, Hn/hc ≤ 4
500 mm section, 3600 mm clear height, class 2, 20 mm bars: max of 500, 600 and 500 is 600 mm, so the end zone is 600 mm; max hoop spacing is min(160, 100) = 100 mm, minimum diameter 8 mm.

How to work it out

  1. Compute the confinement length as the largest of the column's long side, net height ÷ 6, and 500 mm. For a 500 mm column at 3.6 m net height, Hn/6 is 600 mm, so 600 governs.
  2. Treat the base of ground-floor columns separately: confinement extends at least Hn/3, longer than the general-storey rule, because the column base is where plastic hinges form first.
  3. Confine 500 mm above and below rigid ground slabs as well — a provision routinely missed in industrial buildings with hardstanding.
  4. Set the maximum link spacing: class 1 min(6d, 100 mm); class 2 min(8d, 100 mm); classes 3 and 4 min(8d, 150 mm), where d is the main bar diameter.
  5. Set the minimum link diameter: 10 mm for class 1, 8 mm for classes 2 and 3, 6 mm for class 4.
  6. Decide whether full-height confinement applies: corner columns, transfer columns, columns with a shear span ratio of 2 or less, and columns whose net height is no more than four times the long side all require it.

Where it goes wrong

Material and cost

Full-height confinement uses 30-50% more link steel than end confinement alone. A 500×500 column at 3.6 m storey takes about 40 kg of links with end confinement and about 70 kg full height. If only a few columns are involved the extra is small, but misclassifying ordinary columns as full-height adds 3-5% to project-wide reinforcement.

On site

Basis

FAQ

Why confine the ends and not the middle?
Bending moments peak at the ends and plastic hinges form there, so hoops must confine the concrete to keep it from crushing while it dissipates energy. Near mid-height the moment is small and the column is close to pure axial load, so hoops only hold the bars and resist shear - spacing can be relaxed. It is why post-earthquake photos show crushed ends and intact middles.
Why take the largest of three instead of just Hn/6?
Because the governing factor changes with proportions. A stocky 800 mm column has a plastic hinge zone proportional to its depth, so the section governs; a slender tall column is governed by Hn/6; a shallow plant room storey is caught by the 500 mm floor. Each limit guards a different case, so the largest applies.
Where do the 100 mm and 6d limits come from?
They prevent local buckling of the longitudinal bars. Each bar acts as a strut and the hoops are its lateral supports: the closer the supports the less the bar can bow. The 6d limit scales with bar size, 100 mm is the absolute cap, and class 1 uses 6d rather than 8d because those members are expected to reach deeper plastic deformation.