Concrete Cover Thickness Lookup

Minimum cover from exposure class and member type, with every code correction applied.

Quick answer

With the default inputs: Exposure class Class 1 · Member type Slab / wall / shell · Concrete grade C30 etc.Minimum cover c 20 mm

Edit the inputs below to recalculate.

Inputs

Result

Minimum cover c
20mm
Tabulated value15mm
Bar diameter d20mm
Governed by bar diameter (c ≥ d)20mm
Exposure classClass 1 (dry indoor)

Based on GB 50010-2010 (2015 edition) Table 8.2.1 and notes 2-5. Cover is measured from the outer edge of the outermost bar to the concrete surface. Where durability demands are higher, the environment is aggressive, or the design documents say otherwise, the full code and design documents govern.

Formula

Lookupc = Table 8.2.1 (exposure class × member type)
Grade correctionadd 5 mm when concrete is C25 or below
Life correction×1.4 for a 100-year design life, rounded up to 5 mm
Precast5 mm reduction allowed, floors 15 / beams 20
Bar checkc not less than the bar diameter d
Foundation≥40 mm with blinding, ≥70 mm without
Class 2a, beam, C30, 50-year life, cast in situ, 20 mm bars: table gives 25 mm; no grade or life correction; the 20 mm bar does not govern, so cover is 25 mm.

How to work it out

  1. Establish the exposure class first. Class 1 is dry internal (living rooms, bedrooms, offices); class 2a is damp internal or non-severe external (kitchens, bathrooms, canopies); 2b is alternating wet and dry or severe external; 3a is de-icing salt and sea air; 3b is saline soil and coastal. Get this wrong and everything downstream is wrong.
  2. Select by element type: slabs, walls and shells differ from beams, columns and ties, because beams and columns must cover the links, adding 5 mm.
  3. Read the base value: class 1 gives 15 mm for slabs and 20 for beams; 2a gives 20/25; 2b 25/35; 3a 30/40; 3b 40/50.
  4. Adjust for strength: where concrete is C25 or lower, add 5 mm, since low-strength concrete carbonates faster.
  5. Adjust for design life: at 100 years, multiply by 1.4 and round up to the next 5 mm.
  6. Apply the two final checks: cover not less than the bar diameter, and at foundations not less than 40 mm with blinding or 70 mm without.

Where it goes wrong

Material and cost

Every additional 5 mm of cover costs 1-2% more reinforcement because the effective depth reduces and more steel is needed. But rectifying corrosion from inadequate cover costs many times the design difference — repairing a basement soffit can run to several hundred CNY per square metre.

On site

Basis

FAQ

Is cover measured to the stirrup or to the main bar?
To the outermost bar. Where stirrups exist the outermost bar is the stirrup, so cover runs from the stirrup surface to the concrete face and the main bar sits one stirrup diameter deeper. Spacers must be set to the stirrup, which is the most commonly mis-set item on site.
Why add 5 mm for C25 and below?
Lower-grade concrete is less dense and more permeable, so carbonation reaches the bar sooner and the passive layer breaks down. The extra 5 mm compensates. It is also why C20 is rarely used outdoors today - not for lack of strength but for lack of durability.
Is this table enough for coastal or chemical plant structures?
No. This table stops at class 3b. Class 4 (seawater) and class 5 (aggressive substances) are covered by separate codes and usually need coatings, corrosion inhibitors or sulfate-resisting cement as well. Chemical plants, treatment works and marine structures need the specific codes.

Cite this page

Use this format in reports, method statements or coursework. The link is permanent.

Building Calculator. Concrete Cover Thickness Lookup. 2026-10-25. https://jianzhujisuan.com/en/concrete-cover

Results are estimating aids only and are not a design basis. Construction and final accounts must follow the drawings, the applicable standards and an approved method statement. Anything affecting structural safety, shoring or falsework must be checked by a suitably qualified engineer.