Travel Distance to Exit Lookup
Travel distance by occupancy, with all three code corrections.
With the default inputs: Occupancy Other, low or multi-storey · Door position Between two exits · Corridor type Enclosed corridor etc.Maximum travel distance 40 m
Edit the inputs below to recalculate.Inputs
Result
| Tabulated value | 40m |
| Position | Between two exits |
Based on GB 50016-2014 (2018) Table 5.5.17 and notes 1-3. Values are straight-line distances from a room door to the nearest exit. Note 1 adds 5 m for rooms opening onto an open external corridor; note 2 deducts 5 m (between stairs) or 2 m (dead-end) where the route leads to an open stair; note 3 adds 25% where the whole building is sprinklered. Corridor widths, turns, door swing and the separate rules for large retail and audience areas still apply.
Reverse: known result, work out one input
Enter a target result; the other inputs stay fixed and this one is worked out.
Formula
| Lookup | Table 5.5.17 by occupancy × door position |
| Open corridor | add 5 m |
| Open stair | minus 5 m between stairs, minus 2 m at dead ends |
| Sprinklers | add 25% where the whole building is protected |
| Order | apply notes 1 and 2 first, then multiply by 1.25 |
How to work it out
- Establish the occupancy, which sets the base distance. Nurseries and elderly care are strictest, entertainment venues next, then medical buildings (with different values for ward and non-ward areas, and for low-rise versus high-rise), then schools, hotels and exhibition, then other buildings.
- Distinguish door position: between two exits, or on or at the end of a dead-end corridor. Dead-end corridors allow markedly shorter distances because there is only one direction of escape.
- Apply the corridor correction: open external galleries gain 5 m because smoke disperses; where the route leads directly to an open stair, deduct 5 m between two stairs or 2 m on a dead-end corridor, since an open stair can become a smoke path.
- Where the whole building is sprinklered, increase the result by 25%.
- Mind the order: apply the corridor additions and deductions first, then multiply by 1.25. Reversing the order changes the answer.
- Verify the actual travel path measured along the corridor centreline to the nearest exit — not the straight-line distance. Corners and thresholds all count.
Where it goes wrong
- Substituting straight-line distance for the travel path. The real route follows the corridor around columns and bends and is typically 30-50% longer.
- Reversing the order of corrections. Multiplying by 1.25 then adding 5 m differs from adding then multiplying by up to 1.25 m. The code adds first, multiplies second.
- Applying the between-two-exits value to a dead-end corridor. A dead end allows roughly half, because escape is possible in one direction only.
- Applying the 25% uplift for partial sprinkler protection. The code requires the whole building to be protected.
- Forgetting the limit on travel within the room to its door, which is separately regulated at roughly 15-22 m, in addition to the door-to-exit distance.
Material and cost
Remedies for excessive travel distance: add an exit stair (200,000-500,000 CNY each), reconfigure partitions (cheap but disruptive to the layout), or provide a refuge corridor. Settle this at concept stage — discovering it at detailed design usually means redesigning the layout.
On site
- Travel distance starts at the room door, but the distance from the furthest point in the room to that door is separately limited. Both must be satisfied.
- Fire doors and shutters closing during a fire change the route. Assess escape with them closed, never assuming they stay open.
- The 5 m credit for open galleries is conditional: the gallery must genuinely be open with adequate openings. Glazing it in disqualifies the credit.
- Travel distance and exit width are independent criteria, both mandatory. Adequate distance with undersized exits still fails.
Basis
- GB 50016-2014 (2018 edition) Code for fire protection design of buildings, travel distance to exits
- GB 50016-2014 (2018 edition) Code for fire protection design of buildings, means of escape and refuge
- GB 50099-2011 Code for design of schools, means of escape
FAQ
Why is the dead-end distance so much shorter?
Is this straight-line or walking distance?
Is the 25% sprinkler allowance risky?