算BuildCalc

Lighting Level and Fixture Calculator

Lumen method fixture count, achieved lux and power density.

Quick answer

With the default inputs: Room area 50 m² · Target illuminance 300 lx · Lumens per fixture 3000 lm etc.Fixtures required 9 pcs

Edit the inputs below to recalculate.
Length LWidth W
Area is the room's net area and the fitting count is back-calculated by the utilisation-factor method; above 4 m height apply a maintenance factor.

Inputs

m²
lx
Office 300, classroom 300, corridor 100, fine work 500
lm
18 W LED about 1800, 36 W about 3600
0.7-0.8 for light small rooms, 0.4-0.5 for dark large ones
0.8 clean, 0.6 dusty
W

Result

Fixtures required
9pcs
Calculated (unrounded)8.93pcs
Total lumens required15000lm
Effective lumens each1680lm
Achieved illuminance302lx
Illuminance margin0.8%
Total installed power270W
Power density (LPD)5.40W/m²
Area per fixture5.56m²
Spacing in a square grid2.36m

The lumen method suits uniform general lighting and gives average maintained illuminance. Utilisation depends on room index, surface reflectances and luminaire distribution, so exact values come from the manufacturer; the defaults here are for scheme-stage estimates. Power density is a mandatory efficiency metric: offices typically under 9 W/m², retail 10-12, corridors 5.

Formula

Fixture countN = E × A ÷ (Φ × CU × MF)
Achieved levelN × Φ × CU × MF ÷ A
Power densityN × watts ÷ A
Area per fixtureA ÷ N
Square spacing√(A ÷ N)
SymbolsE lux, A area, Φ lumens, CU utilisation, MF maintenance
50 m² at 300 lx with 3000 lm fixtures, 0.7 utilisation, 0.8 maintenance and 30 W: 8.93 calculated, 9 installed, 302 lx achieved, 270 W total and 5.40 W/m².

Illuminance standards and power density limits

SpaceIlluminance lxPower density W/m²Note
Corridors and stairs1005Emergency lighting at least 5 lx
Bedroom756
Kitchen1006300 lx at the worktop
Office3009General office work
Meeting room3009
Classroom3009500 lx on the blackboard
Retail floor30012Good colour rendering needed
Fine machining500—Set by the process
Operating theatre750—Theatre lamp separate

How to work it out

  1. Set the illuminance target first (GB 50034-2013): 100 lx for a living room, 75 lx bedroom, 150 lx dining, 100 lx kitchen and bathroom; 300 lx for offices and classrooms, 500 lx for drafting rooms. These are maintained values on the working plane, not peaks directly under a fitting.
  2. Establish the luminous flux per fitting. LED efficacy is 100-140 lm/W, so a 30 W luminaire is nominally 3000-4200 lm — but use the net output after the diffuser, which loses 10-20%.
  3. Choose the utilisation factor CU: 0.7-0.8 for a light-coloured office, 0.6-0.7 for ordinary finishes, 0.5-0.6 for dark finishes or industrial space. Higher ceilings push it down.
  4. Choose the maintenance factor MF: 0.8 for clean interiors, 0.7 for general, 0.6 for dusty workshops and kitchens.
  5. N = E × A ÷ (Φ × CU × MF), rounded up. A 50 m² office at 300 lx with 3000 lm, CU 0.7 and MF 0.8 gives 8.9, so nine fittings.
  6. Lay them out on a square grid at s = √(A ÷ N) = √(50 ÷ 9) = 2.36 m. The spacing-to-mounting-height ratio should stay between 1.0 and 1.5; beyond that you get visible banding.

Where it goes wrong

Material and cost

30 W LED panels run 60-150 CNY each at project pricing, downlights 40-100, high-bay fittings 150-400, magnetic track heads 200-500. Installation labour is 15-30 CNY per fitting. Designing in 10% spare fittings is much cheaper than retrofitting, which means re-cutting ceilings and re-running cable.

On site

Basis

FAQ

Why does the measured level fall short of design?
Because design values are initial, while luminaires gather dirt and sources age. LEDs lose 20-30% of output in three years and dirty housings another 10-20%, which is what the maintenance factor is for. Plenty of installations pass at handover and measure 60% two years later. Dusty workshops should use 0.6 or even 0.5.
Is more light always better?
No. Beyond what the task needs you get glare, eye strain and wasted energy. Standards grade by task precision: 100 lx in corridors, 300 in offices and classrooms, 500 for fine machining, 750-1000 in operating theatres. Uniformity matters too — the minimum over average should not fall below 0.7, or patchiness proves more tiring than a slightly dim room.
How is power density controlled?
Through efficacy. The same 300 lx needs 20 W/m² with incandescent, 9 with fluorescent and only 5-6 with LED. Codes cap LPD by room type — 9 W/m² for offices, 12 for retail — and exceed it and the job fails sign-off. The right way to cut it is better efficacy and utilisation, through light finishes and good optics, not fewer fixtures and dimmer rooms.

Cite this page

Use this format in reports, method statements or coursework. The link is permanent.

Building Calculator. Lighting Level and Fixture Calculator. 2026-10-25. https://jianzhujisuan.com/en/lighting-lux

Results are estimating aids only and are not a design basis. Construction and final accounts must follow the drawings, the applicable standards and an approved method statement. Anything affecting structural safety, shoring or falsework must be checked by a suitably qualified engineer.