Cable Ampacity Derating Calculator
Temperature, installation and grouping derating in one step.
With the default inputs: Base rating 100 A · Ambient temperature 40 °C · Installation In conduit etc.Usable capacity 78.3 A
Edit the inputs below to recalculate.Inputs
Result
| Temperature factor | 0.87 |
| Installation factor | 0.90 |
| Grouping factor | 1.00 |
| Overall factor | 0.783 |
| Base rating | 100A |
| Capacity lost | 21.7% |
| Three-phase load | 43.8kW |
| Single-phase load | 14.6kW |
| Capacity at 3 grouped | 66.6A |
The three factors multiply rather than add. Three grouped circuits in conduit at 40°C give 0.87 × 0.90 × 0.85 = 0.666, so a 100 A cable is only good for 66.6 A. This is the most commonly missed step: designs account for temperature but forget grouping and conduit, and the cable insulation fails after a year or two in service.
Reverse: known result, work out one input
Enter a target result; the other inputs stay fixed and this one is worked out.
Formula
| Overall factor | kt × kw × kg |
| Usable capacity | base × factor |
| Three-phase load | √3 × U × capacity × cosφ |
| Single-phase load | U × capacity × cosφ |
| Temperature | 1.00 at 30°C, 0.87 at 40, 0.71 at 50 |
| Grouping | 1.00 for one, 0.85 for three, 0.75 for six |
How to work it out
- Look up the base capacity by cable type, core count and cross-section in 19DX101-1 or the manufacturer data. The tabulated conditions are 30°C in free air, single circuit — using the table value directly always overstates reality.
- Temperature factor kt: 1.00 at 30°C, 0.94 at 35, 0.87 at 40, 0.79 at 45, 0.71 at 50. Use the hottest-month mean maximum for the location, not the annual average.
- Installation factor kw: 1.00 in air, 0.90 in conduit, 0.95 on tray, 1.05 direct buried. Buried cables shed heat into soil better than into air, so this one is a credit rather than a penalty.
- Grouping factor kg: 1.00 for one circuit, 0.90 for two, 0.85 for three, 0.80 for four, 0.75 for six. Adjacent circuits heat each other and must be derated.
- Multiply the three factors for the overall K and apply it: actual = base × K. With a 100 A base at 40°C, in conduit, three circuits grouped: 100 × 0.87 × 0.90 × 0.85 = 66.6 A.
- Work back to the load: three-phase P = √3 × U × capacity × cosφ, single-phase P = U × capacity × cosφ. If the load exceeds it, go up a size or improve the installation.
Where it goes wrong
- Reading the catalogue figure and stopping there. Catalogue values assume 30°C, one circuit, free air. Six cables bunched on a tray in summer deliver about 60% of the table value.
- Adding the factors instead of multiplying. 0.87 + 0.90 + 0.85 = 2.62 is absurd; the correct product is 0.665, a factor of four apart.
- Derating a direct-buried cable as if it were in air. Soil has lower thermal resistance, so the same size typically carries 5-15% more buried — provided the depth is adequate and the backfill is not rubble.
- Ignoring solar gain and altitude. A roof-mounted tray in direct sun reaches 70°C at the surface, effectively adding 20°C to ambient; above 2000 m thinner air reduces cooling and requires further derating.
Material and cost
Failing the check means upsizing, which adds 30-60% per size step. Improving heat dissipation is far cheaper: tray dividers, avoiding stacked layers, wider circuit spacing — near zero cost and often worth one or two sizes.
On site
- Stacked tray layers are the most commonly missed item on site. A tray packed solid with cable is a clear violation and the hardest thing to fix once the system is energised.
- Use the hottest-month mean maximum temperature. Correcting against an annual average means no real correction at all in southern summers.
- Fire-rated circuits must be checked for the fire condition (750°C/950°C rated cable); the ordinary temperature correction table does not apply.
- Separate power and control cables with a divider in the same tray, and derate control cables according to the power-cable installation conditions.
Basis
- GB 50217-2018 Standard for design of cables of electric power engineering, cable selection and derating annexes
- GB 50054-2011 Code for design of low voltage distribution, conductor selection
- 19DX101-1 Building electrical data handbook, cable capacity and correction factor tables
FAQ
Why does burying increase capacity?
Why so much derating for grouped cables?
Where do the tabulated ratings come from?
Cite this page
Use this format in reports, method statements or coursework. The link is permanent.
Building Calculator. Cable Ampacity Derating Calculator. 2026-10-25. https://jianzhujisuan.com/en/cable-ampacity