Fire Water Tank Calculator
Indoor plus outdoor plus sprinkler, converted to tank volume.
With the default inputs: Indoor fire demand 20 L/s · Outdoor fire demand 30 L/s · Fire duration 2 h etc.Effective tank volume 468.0 m³
Edit the inputs below to recalculate.Inputs
Result
| Indoor volume | 144.0m³ |
| Outdoor volume | 216.0m³ |
| Sprinkler volume | 108.0m³ |
| Gross demand | 468.0m³ |
| Make-up credit | 0.0m³ |
| Effective volume | 468.0m³ |
| Volume per compartment (2) | 234.0m³ |
| Plan area at design depth | 133.7m² |
| Approximate square side | 11.6m |
Effective volume is indoor, outdoor and sprinkler demand over the fire duration, less water that can be reliably made up during the fire. The 3.6 factor is 1 L/s for 1 h = 3600 L = 3.6 m³. Three cautions: the make-up credit needs a mains supply guaranteed continuous — dual feed with adequate diameter, never a single feed; tanks above 500 m³ should be split into two compartments and above 1000 m³ into two tanks so half the volume stays available during cleaning; and this is the effective volume, so structural volume also needs freeboard (about 0.3 m), the sub-low-water portion required by pump suction, and wall thickness.
Reverse: known result, work out one input
Enter a target result; the other inputs stay fixed and this one is worked out.
Formula
| Indoor volume | V = flow × duration × 3.6 |
| Outdoor volume | V = flow × duration × 3.6 |
| Sprinkler volume | V = flow × duration × 3.6 |
| Make-up credit | V = make-up flow × duration × 3.6 |
| Effective volume | V = indoor + outdoor + sprinkler − make-up |
| Plan area | A = V ÷ effective depth |
How to work it out
- Set the fire duration (GB 50974-2014): 3 h for hydrant systems in high-rise buildings, Class A/B factories and large public buildings, 2 h for other civil buildings; 1 h for automatic sprinkler systems.
- Indoor volume V = indoor flow × duration × 3.6, in m³. The 3.6 converts L/s × h to m³ (3600 ÷ 1000).
- Outdoor volume V = outdoor flow × duration × 3.6. Where the mains cannot guarantee flow and pressure, this volume must also be stored on site.
- Sprinkler volume V = sprinkler flow × sprinkler duration × 3.6.
- Credit reliable make-up during the fire: V = make-up flow × duration × 3.6. This is only permissible with two independent mains connections both guaranteed uninterrupted — never with a single connection.
- Effective volume = indoor + outdoor + sprinkler − make-up; plan area = volume ÷ effective depth, typically 3.5-4.5 m.
Where it goes wrong
- Counting indoor demand only. Where the mains cannot be relied on, the tank must hold indoor and outdoor demand together; omitting outdoor halves the volume and fails fire acceptance outright.
- Assuming make-up is always available and deducting it in full. Only two guaranteed mains connections qualify; deducting against a single connection is effectively falsifying the capacity.
- Taking 2 h for every building. High-rise, large retail and Class A/B factories require 3 h, and one hour short is 50% of the volume — the classic case of discovering the tank is half the required size.
- Forgetting compartmentation. Above 500 m³ the tank must be split into two compartments, each independently maintainable, which increases both footprint and cost over a single-cell estimate.
Material and cost
Reinforced concrete tanks cost 800-1500 CNY/m³ including waterproofing, excavation and base; stainless sectional tanks 1200-2000. A fire tank is a large one-off investment, and remediating an undersized one usually means re-excavating and re-waterproofing at two to three times the original cost.
On site
- Effective volume excludes the suction sump, the freeboard and any portion that must not be drawn by non-fire users. Show both gross and effective figures in the design, or the capacity will be judged insufficient.
- Provide overflow, vent and access manway. The overflow must discharge indirectly and must never connect directly to a sanitary drain.
- Fit anti-vortex devices at pump suction. Insufficient effective depth lets the pump draw air, shown by violently fluctuating pressure gauges and failure to build head.
- In cold regions the tank needs frost protection — earth cover, insulation or an indoor location — with a check that water stays above 5°C in the coldest condition.
Basis
- GB 50974-2014 Technical code for fire protection water supply and hydrant systems, water sources and fire water demand
- GB 50016-2014 (2018 edition) Code for fire protection design of buildings, fire protection installations
- GB 50084-2017 Code for design of sprinkler systems