算BuildCalc

Heating Load Calculator

Load, radiator sections, fuel use and running cost.

Quick answer

With the default inputs: Floor area 100 m² · Storey height 3 · Heat index 60 W/m² etc.Heating load 6.00 kW

Edit the inputs below to recalculate.
Length LWidth W
Area is the heated floor area with internal walls not deducted; the index follows building type, and above 4 m height correct by volume.

Inputs

m²
W/m²
Efficient housing 40-60, ordinary 60-80, public 80-120
°C
°C
days
CNY/m³

Result

Heating load
6.00kW
Building volume300m³
Temperature difference23K
Load per m²60W/m²
Volume method check3.79kW
In kcal/h5160kcal/h
Radiator sections at 120 W50pcs
Gas consumption0.67m³/h
Season gas use971m³
Season cost2718CNY

The area index is an estimate, not a load calculation. A proper calculation takes each envelope element — walls, windows, roof, floor — at its U-value and adds infiltration and ventilation. The index depends heavily on insulation: housing to a 65% energy standard needs only 40-50 W/m² in the same climate where 1980s stock needs 80-100. Retrofit cost hinges on that number.

Formula

Loadarea × heat index in watts
Volume checkvolume × 0.55 × ΔT
Radiator sectionsload ÷ output per section
Gas rateQ × 3.6 ÷ (35.6 × efficiency)
Season usehourly rate × hours/day × days
Units1 kW = 860 kcal/h = 3412 BTU/h
100 m² at 60 W/m², 18°C indoors against −5°C outside over 120 days at 2.8 per m³: 6.00 kW (volume method 3.79 kW), 50 radiator sections, 0.67 m³/h of gas, 971 m³ for the season and about 2718 in cost.

Reference heating indices by building type

Building typeHeat index W/m²Note
Housing (65% efficiency)40-50Built in the last decade
Housing (50% efficiency)50-60Around 2010
Older housing80-100No insulation, single glazing
Office70-100Including ventilation
School, nursery60-80Intermittent use
Retail80-120High fresh-air demand
Hospital80-120Runs 24 hours

How to work it out

  1. Start with the area-index method: Q = floor area × heat index. Dwellings run 40-70 W/m² (high in severe cold zones, low in hot-summer/cold-winter zones), offices 60-80, schools 60-80, retail 80-120.
  2. Cross-check volumetrically: Qv = volume × 0.55 × (tn − tw). Agreement within 20% is fine; a wider gap means the index or the storey height is wrong.
  3. Apply orientation and position corrections: +15-20% for a top floor, +15% for an end unit, +10% for north-facing, another +10% for large glazed areas. Skip this and rooms in the same building end up 5°C apart.
  4. Radiator sections N = load ÷ output per section. A cast-iron four-column 760 gives about 130 W per section at standard conditions; steel panel radiators are rated per unit by the maker, with a correction for low water temperature.
  5. Gas rate V = Q × 3.6 ÷ (35.6 × efficiency). Natural gas has a net calorific value of 35.6 MJ/m³; conventional boilers run 0.85-0.90, condensing 0.95-1.05.
  6. Season consumption is the hourly rate times 8-12 equivalent full-load hours per day times the heating season length; running cost is that volume times the gas price.

Where it goes wrong

Material and cost

A 24 kW gas combi boiler costs 6000-15,000 CNY depending on origin and condensing capability; cast-iron radiators 60-120 CNY per section, steel panels 300-800 per unit. Gas is 2.5-3.5 CNY/m³; a 100 m² dwelling in north China burns 800-1200 m³ over a 120-day season, costing 2000-4000 CNY.

On site

Basis

FAQ

Why does the index vary twofold?
Because insulation levels differ. U-values fall from 1.8 W/(m²·K) for old 240 mm brickwork to 0.4 with external insulation and double glazing — a fourfold gap. Windows are the weak point, losing 40-50% of a house's heat with single glazing, which is why replacing windows usually beats thickening walls.
What indoor temperature is right?
18-20°C is the comfort band for dwellings. Each degree adds 6-8% to energy, so lifting a 100 m² home from 18 to 22 costs an extra 600-800 over a season. Below 16 it is uncomfortable; above 24 the air is dry, occupants get headaches and consumption jumps. Hospitals and public buildings follow their own standards, with theatres at 22-25°C.
Radiators or underfloor heating?
Underfloor runs at 35-45°C supply, feels better with warm feet and cool head, frees the wall, but heats up slowly over 4-6 hours, raises the floor 60-80 mm and is hard to repair. Radiators run at 70-85°C, warm a room in 20 minutes and are easy to service, but take wall space and stir dust. Tight floor-to-ceiling or intermittent use favours radiators; continuous occupation favours underfloor.

Cite this page

Use this format in reports, method statements or coursework. The link is permanent.

Building Calculator. Heating Load Calculator. 2026-10-25. https://jianzhujisuan.com/en/heating-load

Results are estimating aids only and are not a design basis. Construction and final accounts must follow the drawings, the applicable standards and an approved method statement. Anything affecting structural safety, shoring or falsework must be checked by a suitably qualified engineer.