Ringlock Beam Shoring Calculator (Under-Beam Densification)
Under-beam densification: how many rows, which transom size the pitch lands on, jacks and braces.
Also known as beam shoring · under beam support · beam formwork support
With the default inputs: Beam width 0.3 m · Beam depth 0.7 m · Clear span 8 m etc.Total ringlock weight 1.01 t
Use your own dimensions ↓Inputs
Result
| Clear span | 8.0m |
| Beam width | 300mm |
| Beam depth | 700mm |
| Shoring height | 6.0m |
| Beam section | 300×700mm |
| Beam self-weight line load | 5.25kN/m |
| Line load per row | 2.63kN/m |
| Self-weight per standard | 2.36kN |
| Rows along the beam | 9rows |
| Rows across the beam | 2rows |
| Total standards | 18bars |
| Even pitch | 300mm |
| Transom size | B-SG-300 |
| Actual pitch | 300mm |
| Pitch against beam width | 0mm |
| Actual standard length | 5.50m |
| Standard make-up per leg | 3000×1 + 2500×1 |
| Lengths per leg | 2 |
| Total standard splices | 18pcs |
| Standard weight | 485kg |
| Ledger levels | 5levels |
| Transverse ledgers B-SG-300 | 45bars |
| Longitudinal ledgers B-SG-900 | 80bars |
| Ledger weight | 283kg |
| Brace class, Table 6.2.2-1 | Every 3 bays |
| Braces on both beam faces B-XG-900x1500 | 18bars |
| Brace weight | 86kg |
| Head jacks B-ST-600 | 18pcs |
| Base jacks B-XT-600 | 18pcs |
| Head jack projection (limit 400) | 350mm |
| Base jack projection (limit 300) | 0mm |
| Jack weight | 155kg |
| Total component weight | 1009kg |
| In tonnes | 1.01t |
| Steel per metre of beam | 126kg/m |
How this is worked out
Transoms under a beam only come in fixed lengths, so the row pitch is set by what is made, not by what you would like to draw. Ringlock ledgers start at B-SG-300 and step in 300 mm increments up to B-SG-2400. A 300 mm beam with two rows lands exactly on B-SG-300 at 1.30 kg, the leanest arrangement; at 400 or 500 mm the even pitch falls between 300 and 600 and fits neither, so the tool snaps to the nearer size and reports the difference. Snapping to 300 puts the standards inside the beam width and the bearers have to cantilever out; snapping to 600 puts them outside the beam and the head jacks go eccentric. Either way the method statement has to say which. There is no code number for how many rows go under a beam — the codes only require the spacing to come out of the design calculation, and the row count is a design outcome. So the tool does not decide for you; it takes your count and lays out the width each row carries, the size the pitch lands on and how far off it is, which is what tells you whether the arrangement can actually be built. A narrow beam of 200 to 250 mm takes a single centred row, because the shortest ledger is 300 mm and two rows will not fit inside the width. Tie the beam frame to the slab frame. Where an under-beam standard sits within 300 mm of a slab standard the site normally shares one standard and lines the ledgers up at the same level; where they are further apart the two frames stand separately but must still be tied together across the beam with ledgers, never built as two independent scaffolds — clause 6.2.9 requires the shoring either side of an opening to act as one frame, and the same reasoning applies. Braces go on both beam faces, and the tool already counts two. The class still comes from Table 6.2.2-1 using the axial force N and the height, and under a beam N is usually higher than under the slab, so take the worst standard. Beam self-weight is reference only: width times depth times 25 kN/m³, plain concrete, excluding formwork, falsework, construction load and anything coming down from the slab, with no load factors. Deciding whether N is adequate is a load-combination calculation and belongs to the method statement; this tool only takes off quantities. Beams deeper than 700 mm need through-ties on the side forms — see the through-bolt calculator; the deeper the beam the higher the pressure, and the pour rate has to be controlled to match. Standard length follows the same rule as slab shoring: the total must fall between height minus 0.85 m and height minus 0.15 m, with the remainder shared between head jack (up to 400 mm) and base jack (up to 300 mm), and ledger levels are counted with ceil plus one because the closing length needs a ledger of its own. Not included: bearers, joists, soffit and side formwork, through-ties, sole boards and coupler-tube bracing. Standards are made up from only the lengths you tick as in stock — six independent switches for 3.0 / 2.5 / 2.0 / 1.5 / 1.0 / 0.5 m, shared with the facade and shoring pages. Changing the stock changes the make-up, the splice count and the tonnage: at 6.0 m clear height the full set gives a 3000 plus a 2500, while a depot capped at 2.5 m needs 2000 plus 2000 plus 1500 — one extra splice per leg, small in tonnage on a beam frame but still to be staggered lift by lift under clause 6.3.2. This is a take-off, not a substitute for the shoring design or the method statement.
Next up: Ringlock Scaffold Calculator (by component) · Ringlock Shoring Calculator (Slab Soffit)
Reverse: known result, work out one input
Enter a target result; the other inputs stay fixed and this one is worked out.
Formula
| Rows along the beam | n = floor(clear span ÷ spacing along beam) + 1, one at each end |
| Total standards | N = rows along × rows across |
| Even pitch | b = beam width ÷ (rows across - 1) |
| Actual pitch | Snap b to the nearest B-SG fixed size (300-2400 in 300 mm steps) |
| Standard make-up | Complete knapsack over the ticked lengths only (six stock sizes, each switchable), total length between height - 0.85 m and height - 0.15 m; remainder shared by head and base jacks |
| Ledger levels | n = ceil(actual standard length ÷ lift) + 1; the closing length needs a ledger |
| Transverse ledgers | N = levels x rows along x (rows across - 1), sized to the actual pitch |
| Longitudinal ledgers | N = levels x rows across x (rows along - 1), sized to the spacing along the beam |
| Brace class k | From Table 6.2.2-1 by axial force N and height H, as for slab shoring |
| Face braces | N = 2 x [floor((rows along - 1) ÷ k) + 1] x lifts, one plane on each beam face |
| Top lift above 16 m | Braced in every bay above 16 m, with the normal arrangement counting (lifts - 1) |
| Head and base jacks | One of each per standard |
| Beam self-weight line load | gk = width(m) x depth(m) x 25 kN/m³, plain concrete, excluding formwork, live load and load factors |
| Line load per row | gk ÷ rows across (kN/m) |
| Weight | W = sum of quantity x unit mass from Table A.0.1 (kg) |
| Steel per metre of beam | W ÷ clear span (kg ÷ m = kg/m); the clear span is the beam length on this page, not the overall frame width |
How to work it out
- Lay out the rows along the beam: clear span divided by the spacing along the beam, rounded down, plus one, with a row at each end. The spacing along the beam can only be a multiple of 0.3 m — 0.6, 0.9 or 1.2 — because the longitudinal ledgers tying those standards together are fixed-length components. The site habit of 750 mm under a beam comes from coupler scaffolding; ringlock has no such size.
- Decide the number of rows across the beam. There is no code number for this: the codes only require the spacing to come out of the design, and the row count is a design outcome. Two rows for 300 to 500 mm beams, three above 600 mm, a single centred row for 200 to 250 mm. The tool does not decide, but it does show how much beam width each row carries.
- Work out the pitch and snap it to a size. Even pitch is beam width divided by one less than the row count; snap that to the nearest B-SG size. A 300 mm beam on two rows lands exactly on 300 and fits B-SG-300. A 400 or 500 mm beam falls between 300 and 600 and fits neither: snapping to 300 keeps the standards inside the beam and cantilevers the bearers, snapping to 600 puts them outside with eccentric jacks. Either has to be drawn.
- Set the standard length as for slab shoring: total between height minus 0.85 m and height minus 0.15 m, with head and base jacks taking the remainder. Note that the height here is floor to beam soffit, one beam depth lower than under the slab — do not carry over the slab figure.
- Count ledgers. Transverse ledgers run one per standard position along the beam, per level, per pair of adjacent rows, tying the under-beam rows together. Longitudinal ledgers run one per row, per level, per bay, along the beam. Levels are counted with ceil plus one.
- Brace both beam faces. One brace plane on each side, at the class from Table 6.2.2-1 as for slab shoring, continuous from base to top, so the count is two faces times planes times whole lifts. Axial force under a beam is normally higher than under the slab, so take the worst standard.
Where it goes wrong
- Laying out at the architectural beam width without checking the ledger size — transoms are fixed-length and the pitch can only land on 300, 600, 900 and so on. Lay out at 400 and order 400 mm members and no supplier can fill it.
- Entering 750 mm spacing along the beam — the B-SG series starts at 300 and steps by 300, with nothing at 750. Laying out at 0.75 m and ordering 0.9 m leaves 150 mm in every bay, 1.5 m over ten bays, and the last member will not fit. Only coupler scaffolding does 750 mm.
- Taking off the beam alone — when beam and slab are poured together the under-beam standards also carry half a slab bay each side. Sizing on beam self-weight alone understates the axial force badly and drops the brace class a step with it.
- Building the beam frame and slab frame independently — they differ in stiffness and settle differently, so the beam soffit drops first and the side forms crack first. Standards within 300 mm should be shared, and where they are further apart the two frames must at least be tied at every lift.
- Forgetting the second face of braces — an under-beam frame is a narrow strip with two exposed faces, both of which need vertical braces. Counting one face halves the brace order.
- Looking the brace class up from the self-weight figure — 2.36 kN against a design axial force of 15 to 30 kN is an order of magnitude out, before formwork weight, construction load, slab load and load factors. Use the N from the design.
Material and cost
Under-beam ringlock is rented by the tonne-day or square-metre-day, but in practice it is hired as one frame together with the slab shoring, because quoting the beam strip alone makes no sense for delivery and collection. One thing to watch when comparing quotes: densifying under beams raises the average quantity for the whole frame, which is captured when the depot prices by tonne and easily lost when it prices by area, so state the basis in the contract.
On site
- Beams deeper than 700 mm need through-ties in the side forms. Soffit shoring and side-form ties are two independent failure modes: a soffit collapse is a shoring shortfall, a blowout is a tie shortfall. Check both, because checking one is the same as checking neither.
- Bearers must sit centred on the head jack (clause 6.2.4); an eccentric jack tilts the U-head. Snapping the pitch to 600 with the standards outside the beam produces a large eccentricity, and double-channel bearers are the way to bring the load back.
- Never let the standard bear directly on the soffit sheeting: jack, bearer, joist and sheeting are four layers and all four are needed. Skip the joist and the sheeting deflects, leaving honeycomb on the soffit that has to be patched after striking.
- Where a standard clashes with column reinforcement, add a column clamp or shift the row pitch, but do not delete the standard — shear at the beam end is highest exactly where the standard matters most.
- Pour sequence changes what the shoring sees. Pouring the beam first loads the under-beam standards once and then adds the slab; pouring the slab first reverses that. The sequence in the method statement must match the assumption in the shoring check.
- Striking time follows the strength of companion-cured cubes, not the calendar. For beams of 8 m span or less the soffit may come down at 75 per cent of design strength; above 8 m it is 100 per cent.
Basis
- EN 12812:2008 Falsework — Performance requirements and general design
- EN 12813:2004 Temporary works equipment — Load bearing towers of prefabricated components: particular methods of structural design
- BS 5975:2019 Code of practice for temporary works procedures and the permissible stress design of falsework
- ACI 347R-14 Guide to Formwork for Concrete, Chapter 5 (shoring and reshoring of multistorey buildings)
- OSHA 29 CFR 1926.703 (requirements for cast-in-place concrete)
FAQ
How should I set the pitch under a 400 or 500 mm wide beam?
Why can't I enter 750 mm spacing under a beam when that is what we use on site?
Should the beam frame be tied to the slab frame?
Can I use the 2.36 kN self-weight figure directly to look up the brace class?
When the beam and slab are poured together, what gets missed in the shoring take-off?