Voltage Drop Calculator
Percentage voltage drop with a 5% compliance check.
With the default inputs: Load 5 kW · Nominal voltage 380 V · Phase Three phase 380 V etc.Voltage drop 0.76%
Edit the inputs below to recalculate.Inputs
Result
| Design current | 8.94A |
| Loop resistance | 0.2188Ω |
| Voltage drop | 2.88V |
| Voltage at load | 377.1V |
| Limit | 5% |
| Verdict | Pass |
| Max length at this size | 330.1m |
| Min size for 5% | 0.61mm² |
| Drop per 100 m | 1.51% |
The simplified forms ΔU = √3·I·R·cosφ for three phase and 2·I·R·cosφ for single ignore reactance, which is fine below 120 mm². Guidance limits: 5% for lighting and power, relaxed to 8% for temporary site supplies. Excessive drop makes motors hard to start, overheats them and shortens life.
Reverse: known result, work out one input
Enter a target result; the other inputs stay fixed and this one is worked out.
Formula
| Three-phase current | P ÷ (√3 × U × cosφ) |
| Resistance | ρ × L ÷ S |
| Three-phase drop | √3 × I × R × cosφ |
| Single-phase drop | 2 × I × R × cosφ |
| Percentage | ΔU ÷ U × 100 |
| Max length | L × 5 ÷ percentage |
How to work it out
- Compute the current first: three-phase I = P ÷ (√3 × U × cosφ), single-phase I = P ÷ (U × cosφ). Rated current is not operating current — full load and light load differ widely.
- Work out conductor resistance R = ρ × L ÷ S, with ρ = 0.0175 Ω·mm²/m for copper and 0.0283 for aluminium. L is the one-way length.
- Three-phase drop is ΔU = √3 × I × R × cosφ. A single-phase circuit carries current out and back through two conductors, so ΔU = 2 × I × R × cosφ. Dropping that factor of 2 is the classic error.
- Divide by nominal voltage for the percentage. Limits: ±5% at motor terminals, ±5% for other utilisation equipment, -10% to +5% for lighting in general workplaces, and up to 10% momentarily during motor or fire-pump starting.
- If it fails there are three remedies: larger cross-section, shorter run, or a substation moved closer. Copper cost rises with the square of the size while rerouting is nearly free, so check the route first.
- Run it backwards: with a 5% allowance, the maximum feed length is Lmax = L × 5 ÷ drop%, which sets the service radius of a distribution board.
Where it goes wrong
- Counting resistance on one conductor only in a single-phase circuit. Current flows out and back, so omitting the factor of 2 halves the calculated drop and passes a circuit that actually fails.
- Treating 5% as a universal allowance. Lighting ends at -10%, motors get 10% during starting, medical equipment is tighter still. Judging everything against 5% misclassifies real problems.
- Using 20°C resistivity for continuous operation. A fully loaded conductor sits at 60-70°C where copper resistance is about 20% higher, which costs another percentage point on runs beyond 200 m.
- Watching only the percentage and not the absolute volts. A 5% drop on a 24 V control circuit is 1.2 V, enough that a relay will not pull in — control and ELV circuits must be checked in absolute terms.
Material and cost
One size up costs roughly 50% more at 4→6 mm², 60% at 6→10 mm² and 55% at 10→16 mm². On runs beyond 100 m, adding an intermediate distribution board is usually cheaper than upsizing: 800-2000 CNY per board including enclosure, breakers and mounting, at the price of an extra level of discrimination to design.
On site
- Villas, factories and temporary supplies are where this bites: the main board sits at one end, the load 80 m away, and the symptoms are hard-starting motors, contactors chattering, and lights dimming visibly.
- For welders and compressors, sizing on rated current understates the drop. Check the transient with starting current at 4-7 times rated, otherwise every start makes the lights flicker across the whole circuit.
- In a three-phase four-wire system with unbalanced single-phase loads, heavy neutral current shifts the neutral point and pushes terminal voltage further off than the phase-conductor calculation suggests.
- Field rule of thumb: aluminium 16 mm², 100 A over 100 m drops about 8% and definitely fails; copper 16 mm² under the same conditions is about 5%, right on the limit.
Basis
- GB 50052-2009 Code for design of electric power supply systems, voltage deviation and fluctuation
- GB 50054-2011 Code for design of low voltage distribution, protection of distribution circuits
- GB/T 12325-2008 Power quality — deviation of supply voltage
FAQ
Why 2 for single phase and √3 for three?
Why not just use a bigger cable on long runs?
What does low voltage actually do?
Cite this page
Use this format in reports, method statements or coursework. The link is permanent.
Building Calculator. Voltage Drop Calculator. 2026-10-25. https://jianzhujisuan.com/en/voltage-drop